ATMOSPHERIC GAS • PACKAGED WATER HEATER
NICKELSHIELD® - NICKEL-PLATED STORAGE TANK
TANK SERIES 125 GALLONS
Recovery gph c
* Min. Inlet Flow
Gas Pressure
"W.C.
Dimensions
(inches)
Shipping
Weight
lbs
Input
Btu/h
Model Number
40° - 120°F 40° - 140°F
B
C
E
14 N 125A-G
20 N 125A-G
27 N 125A-G
40 N 125A-G
54 N 125A-G
72 N 125A-G
80 N 125A-G
168
239
324
479
648
864
960
134
191
259
383
518
691
768
140,000
199,000
270,000
399,000
540,000
720,000
800,000
4.5
4.5
4.5
4.5
6.5
6.5
7.0
5
6
7
3/4
3/4
3/4
3/4
1
86
86
86
87
87
87
87
980
1030
1090
1170
1330
1430
1490
8
10
12
12
1
1 1/4
c Recoveries based on 80% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
* The information presented is for natural gas 0.6 S.G. – For operation with propane (LP gas), consult the factory.
* For operation outside this range, consult the factory.
Dimensions are in inches unless otherwise notes.
For standard and optional equipment, see form #PV 6070.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC INLET GAS PRESSURE: 14 W.C.
VENTING REQUIREMENTS:
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED
UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.
CHECK NATIONAL FUEL GAS CODE UNDER "ATMOSPHERIC."
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE:
115V, 1Ø, 60 HZ., 2 AMPS
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 5369 07/04
|