Eaton Electrical Power Supply 10000LXL User Manual

 
1. Brief introduction  
1.1 System and model description  
This Online Series is an uninterruptible power supply incorporating  
double-conversion technology. It provides perfect protection  
specifically for computer equipment, Communication Systems to  
computerized instruments.  
Its true online double-conversion design eliminates all mains power  
disturbances. A rectifier converts the alternating current from the  
utility power to direct current. This direct current charges the  
batteries and powers the inverter. On the basis of this DC voltage,  
the inverter generates a pure sinusoidal AC voltage, which is  
modulated by an isolation transformer and then power the loads.  
Computers and Peripherals are thus powered entirely by the UPS. In  
the event of power failure, the maintenance-free batteries power the  
inverter. This manual is applicable to the following models:  
1) The DX 6000L is a standard model with inbuilt battery,  
hereinafter called 6000L;  
2) The DX 6000LXL is a long backup time model, which is able to  
connect with the external battery bank, hereinafter called  
6000LXL;  
3) The DX 10000L is a standard model with inbuilt battery, hereinafter  
called 10000L;  
4) The DX 10000LXL is a long backup time model, which is able to  
connect with the external battery bank, hereinafter called  
10000LXL;  
1.2 Description of commonly used symbols  
The following symbols will be used in this manual and may appear  
during the course of your practical applications. Therefore, all  
users should be familiar with them and understand their meanings.  
1
 
Nation and Explanation  
Nation  
Explanation  
Nation  
Explanation  
Alert you to pay special  
attention  
Protective ground  
Caution of high voltage  
Turn on the UPS  
Alarm silence  
Overload indication  
Idle or shut down the  
UPS  
Battery check  
Recycle  
Alternating current  
source (AC)  
Keep UPS in a clear  
area  
Direct current source  
1.3 Appearance  
Back View Of 6000L(XL)  
2
 
 
Electrical performance  
Input  
Model  
Voltage  
Frequency  
(46~54)/(56~64)Hz  
Output  
Power Factor  
6000L(XL)/  
10000L(XL)  
Single-phase  
>0.98 (Full load)  
Voltage Power  
regulation factor  
Frequency  
tolerance  
Current  
crest ratio  
Distortion Overload capacity  
105%130% load  
transfers to bypass  
mode after 10  
Synchronized  
(46~54)/(56~64)Hz  
in Line mode(AC  
mode)  
THD<3%  
Full load  
(linear  
minutes.  
3:1  
maximum  
±4%  
0.7lag  
>130% load transfers  
to bypass mode after  
1 second and  
±0.1% of normal  
frequency in  
load)  
shutdown the output  
after 1 minutes  
Battery mode.  
Operating environment  
Temperature  
Humidity  
<95%  
Altitude  
<1000m  
Storage temperature  
-15~40℃  
0~40℃  
Note: if the UPS is installed or used in a place where the altitude is  
above than 1000m, the output power must be derated in use, please  
refer to the following :  
Altitude (M)  
1000 1500 2000 2500 3000 3500 4000 4500 5000  
Deratingpower 100% 95% 91% 86% 82% 78% 74% 70% 67%  
4
 
2. Installation  
2.1 Unpacking and inspection  
1) Unpack the packaging and check the package contents. The  
shipping package contains:  
A UPS  
A User Manual  
A Communication Cable  
A Battery Cable (for 6000LXL /10000LXL only)  
2) Inspect the appearance of the UPS to see if there is any  
damage during transportation. Do not turn on the unit and notify  
the carrier and dealer immediately if there is any damage or  
lacking of some parts.  
2.2 Input and output power cords and protective earth  
ground installation  
1. Notes for installation  
1) The UPS must be installed in a location with good ventilation,  
far away from water, inflammable gas and corrosive agents.  
2) Ensure the air vents on the front and rear of the UPS are not  
blocked. Allow at least 0.5m of space on each side.  
3) Condensation to water drops may occur if the UPS is  
unpacked in a very low temperature environment. In this  
case it is necessary to wait until the UPS is fully dried inside  
out before proceeding installation and use. Otherwise there  
are hazards of electric shock.  
Installation and wiring must be performed in accordance with the  
local electric code and the following instructions by professional  
personnel.  
For safety, please cut off the mains power switch before  
5
 
installation. The battery breaker also needs to be cut off if it is a  
long backup time model (XLmodel).  
Open the terminal block cover located on the rear panel of  
the UPS, please refer to the appearance diagram.  
For 6000L(XL) UPS, it is recommended to select the  
UL101510AWG(6mm2) wire or other insulated wire which  
complies with AWG Standard for the UPS input and output  
wirings.  
For 10000L(XL) UPS, it is recommended to select the  
UL1015 8AWG(10mm2) wire or other insulated wire which  
complies with AWG Standard for the UPS input and output  
wirings.  
Note: Do not use the wall receptacle as the input power source  
for the UPS, as its rated current is less than the UPSs  
maximum input current. Otherwise the receptacle may be  
burned and destroyed.  
Connect the input and output wires to the corresponding  
input and output terminals according to the following  
diagram.  
Note: you must make sure that the input and output wires and the  
input and output terminals are connected tightly  
The protective earth ground wire refers to the wire  
connection between the equipment which consumes electric  
equipment and the ground wire. The wire diameter of  
protective earth ground wire should be at least as above  
mentioned for each model and green wire or green wire with  
yellow ribbon wire is used.  
After having completed the installation, make sure the  
wiring is correct.  
Please install the leak current protective breaker at the output  
power distribution panel of the UPS if necessary.  
6
 
To connect the load with the UPS, please turn off all the loads  
first, then perform the connection and finally turn on the loads  
one by one.  
No matter the UPS is connected to the utility power or not,  
the output of the UPS may have electricity. The parts inside  
the unit may still have hazardous voltage after turning off the  
UPS. To make the UPS have no output, power off the UPS,  
and then disconnect the utility power supply.  
Suggest charging the batteries for 8 hours before use. After  
connection, turn the bypass breaker in the ONposition, the  
UPS will charge the batteries automatically. You can also use  
the UPS immediately without charging the batteries first, but  
the backup time may be less than the standard value.  
If it is necessary to connect the inductance load such as a  
monitor or a laser printer to the UPS, the start-up power  
should be used for calculating the capacity of the UPS, as its  
start-up power consumption is too big when it is started.  
Input and output Terminal Block wiring diagram of 6000L(XL)/10000L(XL)  
Important notes: If the UPS is used in single mode, JPI and JP2  
must be connected by 10AWG(6mm2). If the UPS is used in  
parallel mode, the Jumper between JP1 and JP2 must be removed  
7
 
Connection Details of Output Terminals  
Important Note: If the UPS is used in Single Mode, JP1 and JP2  
must be connected by 10AWG (6mm2). If the UPS is used in Parallel  
Mode, the Jumper between JP1 and JP2 must be removed.  
Option: 1  
Connection Details of Output Terminals.  
Connection Details of Output Terminals.  
Connect Output Line 1 and Output Neutral 1 for 120V / 3KVA Load or connect by  
10AWG (6mm2). Output Line 2 and Output Neutral 2 for 120V / 3KVA Load.  
8
 
Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be  
connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper  
between JP1 and JP2 must be removed.  
Option: 2  
Connection Details of Output Terminals.  
Connect Output Line 1 and Neutral2 by 10AWG (6mm2) for 240V / 6KVA Load.  
Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be  
connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper  
between JP1 and JP2 must be removed.  
2.3 Operating procedure for connecting the long backup  
time model UPS with the external battery  
1. The nominal DC voltage of external battery pack is 240VDC.  
Each battery pack consists of 20 pieces of 12V maintenance free  
batteries in series. To achieve longer back time, it is possible to  
connect multi-battery packs, but the principle of same voltage,  
same typeshould be strictly followed.  
2. The connector of the external battery cable is used to plug into  
the external battery socket of the UPS, the other end of the  
external battery cable is made of three open wires with ring  
terminals to connect with the external battery pack(s). The  
procedure of installing battery bank should be complied with  
strictly. Otherwise you may encounter the hazardous of electric  
shock.  
9
 
1) DC breaker must be connected between the battery pack and  
the UPS. The capacity of breaker must be not less than the data  
specified in the general specification.  
2) Set the battery pack breaker in OFFposition and connect the  
20 pieces of batteries in series  
3) You must connect the external battery cable to the battery first,  
if you connect the cable to the UPS first, you may encounter the  
hazardous of electric shock. The positive pole of the battery is  
connected to the10000LXL in parallel with blue and brown wires;  
the negative pole of the battery is connected to the 10000LXL in  
parallel with black and white wires; the green and yellow ribbon  
wire is connected to the ground of the battery cabinet.  
3. To complete the connection by plugging the connector of the  
external battery cable into the external battery socket of the UPS.  
Do not attempt to connect any loads to the UPS now. You should  
connect the input power wire to the right position first. And then  
set the breaker of the battery pack in the ON position. After that  
set the bypass breaker in the ON position. The UPS begins to  
charge the battery packs at the time.  
The blue & brown wires for connection to the positive  
terminal of the battery pack output  
The black & white wires for  
connection to the negative  
terminal of the battery pack  
The receptacle for  
The green and yellow ribbon wire for  
connecting the UPS  
connection to the ground of the battery  
cabinet  
The External Battery Cable Diagram For 6000L(XL)/10000L(XL)  
(The cable may vary from different XLmodels)  
10  
 
2.4 Parallel operation  
1. Brief introduction of the redundancy  
N+X is currently the most reliable power supply structure. N  
represents the minimum UPS number that the total load needs; X  
represents the redundant UPS number, i.e. the fault UPS number  
that the system can handle simultaneously. The bigger the X is, the  
higher reliability of the power system is. For occasions where  
reliability is highly depended on, N+X is the optimal mode.  
As long as the UPS is equipped with parallel cables, up to 3 UPSs  
can be connected in parallel to realize output power sharing and  
power redundancy.  
2. Parallel installation  
1) Users need to opt a standard 25-pin communication cable,  
which should have 25 cores, corresponding stitches and shield,  
as the UPS parallel cable. The length of the parallel cable is  
appropriate to be less than 3 m.  
2) Strictly follow the stand-alone wiring requirement to perform the  
input wiring of each UPS.  
3) Connect the output wires of each UPS to an output breaker  
panel.  
4) Disconnect the Jumper on JP1 and JP2 of the terminal block  
first, and connect each output breaker to a main output breaker  
and then to the loads.  
Note: The requirement of the output wiring is as follows:  
When the distance between the UPSs in parallel and the breaker  
panel is less than 20 meters, the difference between the wires of  
input & output of the UPSs is required to be less than 20%;  
When the distance between the UPSs in parallel and the breaker  
panel is greater than 20 meters, the difference between the wires  
of input & output of the UPSs is required to be less than 10%.  
11  
 
3. Parallel operation  
To perform the general operation, follow the stand-alone operating  
requirement:  
1) Startup: The units transfer to INV mode simultaneously as they  
start up sequentially in utility power mode;  
2) Shutdown: the units shut down sequentially in INV mode. When  
the l ast one completes the shutdown action, each unit will shut  
down the inverter simultaneously and transfer to bypass mode.  
It is easy to operate the equipment, with no previous training. You  
just need to read through this manual and operate according to the  
instructions in it. The meaning of the LED indicators, please refer to  
the appendix 1 Display panel”  
3. Operation and Operating mode  
3.1 Operation  
1. Turn on the UPS with utility power supplied (in Line mode/AC  
mode)  
1) After you make sure that the power supply connection is correct,  
set the bypass breaker and the input breaker in the ON”  
position first. At this time the fan rotates and the UPS  
supplies power to the load via the bypass. The UPS operates  
in Bypass mode.  
12  
 
2) To power on the UPS by simply pressing the ONbutton  
continuously for more than 1 second.  
3) When being powered on, the UPS will perform self-diagnosis,  
with the load/battery level LEDs turned on and then off one  
after another in ascending order. A few seconds later, the INV  
LED is turned on, the UPS is already running in Utility Power  
mode. If the utility power is abnormal, the UPS will operate in  
battery mode without output interruption of the UPS.  
2. Turn on the UPS with no utility power supplied (in Battery mode)  
1) Press the ONbutton continuously for more than 1 second to  
power on the UPS. For long back up time model (XLmodel),  
please make sure that the battery breaker is in ONposition.  
2) During the course of starting up, the UPS has the same action  
as if it is connected to utility power except that the utility power  
LED is not turned on and the battery LED is turned on instead.  
3. Turn off the UPS with utility power supplied (in Line mode/AC mode)  
1) Press the OFFbutton continuously for more than 1 second  
to turn off the inverter of the UPS immediately.  
2) When being powered off, the UPS will perform self-diagnosis,  
the Load/Battery level LEDs will be turned on and then off one  
after another in ascending order, then the INV LED will be  
turned off and Bypass LED will be turned on. The UPS is  
working in Bypass mode.  
3) Upon completion of the above to turn it off, output of electric  
current of the UPS is still present. In order to cut off the output  
from the UPS, simply cut off the utility power supply and the  
UPS will perform self-diagnosis, finally not any display is  
shown on the display panel and no voltage output is available  
from the UPS output.  
4. Turn off the UPS with no utility power supplied (in Battery mode)  
1) Press the OFFbutton continuously for more than 1 second  
13  
 
to power off the UPS.  
2) When being powered off, the UPS will perform self-diagnosis,  
the Load/Battery level LEDs will be turned on and then off one  
after another in ascending order. Finally not any display is  
shown on the display panel and no voltage is available from  
the UPS output.  
Suggestions: Please turn off the connected loads before turning on  
the UPS and turn on the loads one by one after the UPS is working  
in INV mode. Turn off all of the connected loads before turning off  
the UPS.  
3.2 Operating mode  
1. Utility power mode  
The display panel in utility power  
mode is shown in the following  
diagram. The utility power LED and  
the INV LED are turned on. The  
load level LEDs will be turnd on in  
accordance with the load capacity  
connected.  
1) If the battery LED is turned on  
and the utility power LED  
The Utility Power Mode  
flashes, it indicates the voltage  
or frequency of the utility power  
has exceeded the normal range, the UPS operates in battery  
mode.  
2) If output overloaded, the load level LEDs will be turned on and  
alarm will keep twice every second. You should get rid of some  
unnecessary loads one by one to decrease the loads connected  
to the UPS less than 90% of its nominal power capacity.  
Note: Please follow the following steps to connect the generator:  
Activate the generator and wait until the operation is stable  
14  
 
before supplying power of the generator to the UPS (be sure  
that the UPS is in idle mode). Then turn on the UPS according to  
the start-up procedure. After the UPS is turned on, then the  
loads can be connected to the UPS one by one.  
The power capacity of the AC generator should be at least twice  
of the UPS capacity.  
2. Battery mode  
The display panel in battery mode is shown in the following diagram.  
The battery LED and the INV LED are turned on. The displayed  
number of the battery level LEDs will be turned on in accordance  
with the battery capacity. Note that the load level LEDs in utility  
power mode will indicate the level of  
the battery capacity in battery mode.  
1) When the UPS in battery mode,  
the buzzer beeps once every 4  
seconds. If the ONbutton is  
pressed for more than  
1
seconds, the buzzer will stop  
beeping. Press the ONbutton  
once again for more than 1  
second to resume the alarm  
function.  
Battery mode diagram  
2) When the battery capacity  
decreases, the number of the battery capacity LEDs turned on  
will be reduced. If the battery voltage descends to the alarm  
level, the buzzer will beep once every second to remind the  
users of in sufficient battery capacity and the UPS is soon  
going to shut down automatically. Then the load operations  
should be carried out promptly and the loads should be  
eliminated one by one.  
3. Bypass mode  
15  
 
The display panel in bypass mode is  
shown in the following diagram. The  
utility power LED and the bypass  
LED are lit. The displayed number  
of the load LEDs will be turned on in  
accordance with the load capacity  
connected. The UPS will beep once  
every 2 minutes in bypass mode.  
1) The utility power LED flashes, it  
shows that the voltage or  
frequency of the utility power  
has exceeded the normal range  
of the UPS.  
Bypass Mode Diagram  
2) Other indications on the display panel are the same in utility  
mode.  
3) The UPS does not have the backup function when it is in  
bypass mode. The power used by the load is supplied from the  
utility power via internal filter and the transformer.  
4. Abnormality mode  
In case the fault LED is turned on when the UPS is in use, it shows  
that the UPS is operating in abnormal mode. Please refer to the  
troubleshooting in section 6 for detail.  
5. Backup time for the standard model  
The backup time of the long backup time model is dependent on the  
external battery pack capacity and the load level as well as other  
factors. The backup time of standard model may vary from different  
models and load level. Please refer to the following:  
16  
 
Load Level  
Load level  
Backup Time Of 6000L(XL)  
Backup Time Of 10000L(XL)  
6. Communication Port  
Intelligent slot  
This series is equipped with an intelligent slot for Webpower  
(optional accessory) or other optional card to achieve remote  
management of the UPS through internet / intranet. Please contact  
your local distributor for further information.  
RS232 interface  
The following are the descriptions and pin assignment of RS232  
DB-9 port:  
Baud rate: 2400bps  
Ending bit:1bit  
Data bit: 8 bit  
Parity bit: None  
17  
 
Pin  
Function  
I/O  
number  
description  
3
2
5
Rx  
Tx  
input  
output  
GND  
Ground  
DB-9 pin assignment:  
RS232 Interface  
Optional AS400 interface  
This optional AS400 card provides dry contact closure signal  
OPENor CLOSE. Following are the pin assignment and the  
descriptions of AS400 card:  
PIN1: UPS failure (normally open, active close)  
PIN2: summary alarm  
PIN3: ground  
PIN4: Remote shutdown  
PIN5: Common  
PIN6: Bypass active (relay close)  
PIN7: Battery low  
PIN8: UPS On (relay close)  
PIN9: Utility Power failure (normally open, active close)  
AS400 Interface  
18  
 
Data-Line Surge Protection  
The built-in data-line surge  
suppression on the rear panel  
completes your system protection. It  
provides an easy way to protect a  
network (RJ45) or modem (single line  
phone) connection from hazardous  
spikes.  
RJ45  
4. Battery maintenance  
This series UPS only requires minimal maintenance. The battery  
used for standard models are value regulated sealed lead-acid  
maintenance free battery. These models require minimal repairs.  
The only requirement is to charge the UPS regularly in order to  
maximize the expected life of the battery. When being connected to  
the utility power, whether the UPS is turned on or not, the UPS keeps  
charging the batteries and also offers the protective function of  
overcharging and overdischarging.  
The UPS should be charged once every 4 to 6 months if it has not  
been used for a long time.  
In the regions of hot climates, the battery should be charged and  
discharged every 2 months. The standard charging time should be at  
least 12 hours.  
Under normal conditions, the battery life lasts 3 to 5 years. In case if  
the battery is found not in good condition, earlier replacement should  
be made. Battery replacement should be performed by qualified  
personnel.  
19  
 
Replace batteries with the same number and same type of batteries.  
Do not replace the battery individually. All the batteries should be  
replaced at the same time following the instructions of the battery  
supplier.  
Normally, the batteries should be charged and discharged once  
every 4 to 6 months. Charging should begin after the UPS shuts  
down automatically in the course of discharging, the standard  
charging time for the standard UPS should be at least 12 hours.  
5. Notes for battery disposal and battery  
replacement  
1) Before disposing of batteries, remove conductive jewelry  
such as necklace, wrist watches and rings.  
2) If it is necessary to replace any connection cables, please  
purchase the original materials from the authorized  
distributors or service centers, so as to avoid overheat or  
spark resulting in fire due to insufficient capacity.  
3) Do not dispose of batteries or battery packs in a fire, or they  
may explode.  
4) Do not open or mutilate batteries, released electrolyte is  
highly poisonous and harmful to the skin and eyes.  
5) Do not short the positive and negative of the battery  
electrode, otherwise, it may result in electric shock or fire.  
6) Make sure that there is no voltage before touching the  
batteries. The battery circuit is not isolated from the input  
potential circuit. There may be hazardous voltage between  
the battery terminals and the ground.  
7) Even though the input breaker is disconnected, the  
components inside the UPS are still connected with the  
batteries, and there are potential hazardous voltages.  
20  
 
Therefore, before any maintenance and repairs work is  
carried out, switch off the breaker of the battery pack or  
disconnect the jumper wire of connecting between the  
batteries.  
8) Batteries contain hazardous voltage and current. Battery  
maintenance such as the battery replacement must be  
carried out by qualified personnel who are knowledgeable  
about batteries. No other persons should handle the  
batteries.  
6. Troubleshooting  
Problem  
Possible cause  
Solution  
Make sure the UPS is not overloaded;  
the air vents are not blocked and the  
ambient temperature is not too high.  
Wait for 10 minutes for the UPS to cool  
down before turning on again. If failed,  
please contact the distributor or service  
center.  
The #1 Fault LED  
and the #6 LED are The UPS  
turned on, the  
buzzer beeps  
continuously  
shutdown due to  
internal overheat  
The #1 Fault LED  
and the #2 and #5  
LED are turned on,  
and the buzzer  
Turn off the UPS. Remove all the loads.  
Ensure that the load is not failed or the  
UPS has no internal faults before  
turning it on again. If failed, please  
contact the distributor or service center.  
The UPS output  
is short circuited.  
beeps continuously  
The #1 Fault LED  
and the #4 LED are  
turned on, the UPS  
beeps continuously  
The #1 Fault LED  
and the #5 LED are  
turned on, the UPS  
beeps continuously  
The #1 Fault LED  
The UPS shuts  
down due to its  
internal fault.  
Please contact the distributor or service  
center.  
The UPS shuts  
down due to its  
internal fault.  
Please contact the distributor or service  
center.  
and the #3 LED are Overcharging  
The charger of the UPS is failed. Please  
contact the distributor or service center.  
protection  
turned on, the UPS  
beeps continuously  
21  
 
The voltage or  
frequency of the  
utility power is  
out of the input  
range of the  
UPS.  
The UPS is running in battery mode. To  
save your data and close the application  
program. Make sure the utility power is  
within the input voltage or frequency  
range permitted by the UPS.  
The utility power  
LED flashes  
Check the loads and remove all  
no-critical equipment. Recalculate the  
load power and reduce the number of  
loads connected to the UPS. Check that  
the loads are not failed.  
The #1 Fault LED  
The UPS is  
and the #2 LED are overloaded or the  
turned on, the UPS load equipment  
beeps continuously is faulty  
22  
 
The #1 Fault LED  
and the battery LED  
are turned on, the  
buzzer beeps every  
second  
The charger of  
the UPS is  
defective.  
Please contact the distributor or service  
center.  
Check the battery. If the battery is  
damaged, replace the battery  
Battery low or  
battery not  
connected  
Battery LED flashes  
immediately and ensure that the battery  
breaker is in ONposition.  
The utility power is  
normal, but the UPS  
can not turn in line  
mode  
Bypass breaker  
Set the bypass breaker in ONposition.  
in OFFposition  
Battery not yet  
been fully  
Keep UPS connected to utility power  
persistently for more than 10 hours to  
recharge the batteries again.  
charged  
Battery discharging  
time diminishes  
Check the loads and remove the  
non-critical equipment.  
UPS overloaded  
Replace the batteries. Please contact  
the distributor to obtain the parts and  
replacement service.  
Battery aged  
The ONbutton  
is pressed too  
briefly  
Press the ONbutton for more than 1  
second.  
The UPS is not  
connected to the  
battery or the  
battery pack  
voltage is too  
low.  
The UPS cannot  
power on after  
pressing the ON  
button  
Check the battery or recharge the  
battery.  
Please contact the distributor or service  
center.  
UPS fault  
When you contact the service center, please provide the following information:  
Model No. and the serial No. of the UPS;  
The date when the problem arose;  
Complete description of the problem, including the LED display, alarm warning,  
and power condition and load capacity. If your UPS is a long backup time model,  
you may also provide the battery information.  
23  
 
Appendix 1display panel  
n
Power ON/OFF: To turn on the UPS simply by pressing the ONbutton on the  
front panel continuously for 1 second. Press the OFFbutton on the front panel  
continuously for 1 second to turn off the UPS.  
n
n
n
n
n
n
Bypass LED (orange LED): Whenever the bypass LED is turned on, it shows  
that the loading current is supplied directly from the utility power.  
Utility power LED (green LED): Whenever the utility power LED is turned on, it  
shows that the utility power is normal.  
Inv LED (green LED): Whenever the INV LED is turned on, it shows that the  
loading current is supplied from utility power or battery via the inverter.  
Battery LED (orange LED): Whenever the battery LED is turned on, it shows  
that the loading current is supplied from battery via the inverter.  
Fault LED (red LED): Whenever the fault LED is turned on, it shows that the  
UPS is in abnormal condition.  
#2-#6 LEDs (the #2 LED is orange and the #3-#6 LEDs are green): These  
LEDs indicate the percentage of the load capacity in utility power mode or  
battery capacity level in battery mode.  
24  
 
Appendix 2The corresponding form of the LED  
display  
LED display  
Alarm  
warning  
No.  
Operating state  
1# 2# 3# 4# 5# 6# 7# 8# 9# 10#  
0~35%  
Load capacity  
1
2
3
4
5
none  
none  
none  
none  
none  
36%~55%  
Load capacity  
Utility  
Power  
Mode  
56%~75%  
Load capacity  
76%~95%  
Load capacity  
96%~105%  
Load capacity  
0~20%  
Battery  
capacity  
Beep once  
every sec  
6
7
21%~40%  
Battery  
capacity  
Beep once  
every 4 sec  
41%~60%  
Battery  
capacity  
Battery  
Mode  
Beep once  
every 4 sec  
8
61%~80%  
Battery  
capacity  
Beep once  
every 4 sec  
9
81%~100%  
Battery  
capacity  
Beep once  
every 4 sec  
10  
Beep once  
every 2 min.  
11 Bypass mode  
Overloaded in utility  
12 mode and UPS still in  
INV mode  
Beep twice  
every sec.  
Overloaded in utility  
mode and UPS in  
bypass mode  
Continuously  
beep  
13  
25  
 
14 Utility power abnormal  
Overloaded in battery  
Beep twice  
every sec.  
mode,  
15  
Early-warning  
Overloaded in battery  
mode,  
Continuously  
beep  
16  
Cut off the output  
Continuously  
beep  
17 Over temperature  
18 Inv abnormal  
Continuously  
beep  
Continuously  
beep  
19 Output short circuited  
20 BUS voltage abnormal  
21 Charger or battery failed  
Continuously  
beep  
Continuously  
beep  
Battery voltage  
abnormal  
22  
Continuously  
beep  
23 BAT SCR failed  
24 Fan abnormal  
25 Bypass STS failed  
26 INV RLY failed  
Continuously  
beep  
Continuously  
beep  
Continuously  
beep  
Communication  
abnormal  
Continuously  
beep  
27  
: Solid ON  
: Flash  
: LED display and alarm warning are dependent on other conditions.  
26  
 
614-03753-01  
 

Continental Electric Toaster CE23451 User Manual
Creda Oven J052E User Manual
Cuisinart Cooktop CSB 77 User Manual
Ducane Gas Grill 20529915 User Manual
Duracell Battery Charger 146E User Manual
DXG Technology Digital Camera DXG 518 User Manual
Edelbrock Automobile Accessories 68003 User Manual
Electro Voice Speaker SH 1800 User Manual
Garland Range PS 8 User Manual
Global Machinery Company Saw SYT210 User Manual